CVE-2022-29922: A vulnerability exists in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS ...

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

HighCVSS 7.5Not KEV-listedUpdated
Glexia's TakeAutomated analysishigh

Security readout for executives and security teams

Plain-English summary

This flaw can crash or disrupt the IEC 61850 OPC Server component in affected Hitachi Energy SYS600 MicroSCADA products. It is availability-only but important because SYS600 is used in operational technology environments where loss of SCADA server functions can affect monitoring and control workflows.

Executive priority

Treat as high priority for affected OT environments because an unauthenticated network condition can disrupt SCADA server availability. Prioritize systems that support critical operations or are reachable across weak segmentation.

Technical view

CVE-2022-29922 is improper input validation in Hitachi Energy MicroSCADA X SYS600 and MicroSCADA Pro SYS600. A specially crafted IEC 61850 packet with a valid data item but incorrect data type can cause denial of service in the IEC 61850 OPC Server. CVSS 3.1 is 7.5, network exploitable, no authentication or user interaction required.

Likely exposure

Exposure is most likely in utilities or industrial environments running MicroSCADA Pro SYS600 9.4 FP2 Hotfix 4 or earlier, or MicroSCADA X SYS600 10 through 10.3.1, especially where the IEC 61850 OPC Server is reachable from untrusted or weakly segmented networks.

Exploitation context

The supplied sources do not show CISA KEV listing or cited active exploitation. The risk comes from unauthenticated network reachability and high availability impact, not from confirmed exploitation in the bundle.

Researcher notes

The bundle identifies CWE-20 and an availability impact only. It does not provide exploit details, proof of active exploitation, or fixed-version text beyond the Hitachi Energy advisory reference. Validation should focus on affected versions, component exposure, and vendor guidance.

Mitigation direction

  • Identify all SYS600 deployments and confirm product, version, and enabled IEC 61850 OPC Server use.
  • Review the Hitachi Energy advisory for supported fixes or vendor-approved mitigations.
  • Apply vendor-recommended updates or mitigations through normal OT change-control processes.
  • Restrict IEC 61850 OPC Server reachability to trusted control-network paths where operationally feasible.
  • Increase monitoring for unexpected SYS600 OPC Server crashes or restarts.

Validation and detection

  • Check asset inventory for MicroSCADA Pro SYS600 and MicroSCADA X SYS600 versions listed as affected.
  • Confirm whether the IEC 61850 OPC Server component is installed, enabled, and network reachable.
  • Map allowed network paths to the OPC Server from engineering, control, and external zones.
  • Review operational logs for unexplained denial-of-service symptoms or service restarts.
  • Document remediation status against the Hitachi Energy advisory.
Prepared
Confidence
high
Sources
3

Generated from the cited source records. This long-tail analysis has not been individually reviewed by a named human.

Potential ATT&CK relevance

Conservative CVE-to-ATT&CK context

These mappings and lookup hints may be relevant to the vulnerability behavior, CWE, affected product, or exposure path. Glexia-inferred context is not an official MITRE, ATT&CK, CWE, or CVE Program mapping.

ATT&CK lookup starting points

Use these exact CWE pages and searches to review the Glexia ATT&CK library from this CVE's weakness and description context.

cwe · low confidence lookup

CWE-20: Exact CWE lookup

Use the exact CWE identifier as the starting point before reviewing related ATT&CK behavior. Open the exact CWE lookup page first, then review the ATT&CK searches from that MITRE weakness context. This is a Glexia lookup hint, not an official ATT&CK mapping.

Open ATT&CK lookup
cve · low confidence lookup

CVE-2022-29922 mapping review

Open the CVE-to-ATT&CK bridge for reviewed, inferred, or future official mappings tied to this CVE.

Open ATT&CK lookup
Vulnerability profileCVE Program record
Severity
High
CVSS
7.5 (3.1)
Known Exploited
No
Published

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Official CVE source material

CNA and ADP enrichment extracted from CVE v5

These fields come from the CVE record and ADP containers, not from Glexia's Take. They preserve time-varying source decisions such as CISA SSVC, KEV status, CVSS metrics, and provider references.

1CVSS vectors
0Timeline events
0ADP providers
2Source links

CVSS vector scores

1 official score

We collect every scored CVSS vector available in the official CNA and ADP containers. When more than one version is present, the table keeps the source vectors side by side instead of collapsing them into the highest score.

ScoreVersionSeverityVectorExploitImpactSource
7.5CVSS 3.1HighCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H3.93.6Primary CVE score

Vulnerability scoring details

Base CVSS 3.1 score

7.5High
CVSS 3.1 vector shape for CVE-2022-29922Attack VectorAttack ComplexityPrivileges RequiredUser InteractionScopeConfidentiality ImpactIntegrity ImpactAvailability Impact

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Attack Vector
NetworkAdjacentLocalPhysical
Attack Complexity
LowHigh
Privileges Required
NoneLowHigh
User Interaction
NoneRequired
Scope
ChangedUnchanged
Confidentiality Impact
HighLowNone
Integrity Impact
HighLowNone
Availability Impact
HighLowNone
Affected products

Products and packages named in the record

VendorProductVersion / packageStatus
Hitachi EnergyMicroSCADA X SYS60010, 10.1, 10.1.1, 10.2, 10.2.1, 10.3, 10.3.1Listed
Hitachi EnergyMicroSCADA Pro SYS600unspecifiedListed
Weakness

CWE details

CWE links open Glexia weakness intelligence pages with official CWE context, developer remediation guidance, and related CVE mappings.

CWE-20 · source CWE mapping

Improper Input Validation

Improper Input Validation represents a recurring weakness pattern that can create exploitable paths when design, validation, or implementation controls are missing.