LiveActive security incident?Get immediate response
CVE Record

CVE-2021-27383: A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl.

A vulnerability has been identified in SIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants) (All versions < V15.1 Update 6), SIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Update 6), SIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V16 Update 4), SIMATIC WinCC Runtime Advanced V15 (All versions < V15.1 Update 6), SIMATIC WinCC Runtime Advanced V16 (All versions < V16 Update 4), SINAMICS GH150 (All versions), SINAMICS GL150 (with option X30) (All versions), SINAMICS GM150 (with option X30) (All versions), SINAMICS SH150 (All versions), SINAMICS SL150 (All versions), SINAMICS SM120 (All versions), SINAMICS SM150 (All versions), SINAMICS SM150i (All versions). SmartVNC has a heap allocation leak vulnerability in the server Tight encoder, which could result in a Denial-of-Service condition.

HighCVSS 7.5Not KEV-listedUpdated
Glexia's TakeAutomated analysishigh

Security readout for executives and security teams

Plain-English summary

This flaw can let an unauthenticated network attacker exhaust resources in Siemens HMI, WinCC Runtime Advanced, and listed SINAMICS systems using SmartVNC, causing a denial of service. The business concern is loss of operator visibility or control interface availability, not data theft.

Executive priority

Treat as a high-priority OT availability issue where affected systems support production, safety monitoring, or operator workflows. Prioritize remediation by exposure and process criticality, with special attention to remotely reachable SmartVNC services.

Technical view

SmartVNC has a heap allocation leak in the server Tight encoder. The CVSS 3.1 score is 7.5 with network access, low complexity, no privileges, no user interaction, and high availability impact only. The weakness is mapped to CWE-770.

Likely exposure

Exposure is most likely in OT environments running the listed Siemens SIMATIC HMI panels, WinCC Runtime Advanced V15/V16, or SINAMICS variants, especially where SmartVNC is reachable from broad plant, corporate, or remote-access networks.

Exploitation context

The provided bundle does not show CISA KEV listing or cited evidence of active exploitation. The risk remains operationally significant because the vector is network-reachable, unauthenticated, and targets availability in industrial systems.

Researcher notes

The source bundle identifies many Siemens product lines but only gives explicit fixed thresholds for V15 and V16 HMI and WinCC Runtime Advanced. It does not provide exploit details, active exploitation evidence, or complete remediation detail for SINAMICS all-version entries.

Mitigation direction

  • Inventory all listed Siemens HMI, WinCC, and SINAMICS assets.
  • Update V15 HMI and WinCC systems to V15.1 Update 6 or later.
  • Update V16 HMI and WinCC systems to V16 Update 4 or later.
  • For SINAMICS entries marked all versions, follow current Siemens advisory guidance.
  • Restrict SmartVNC exposure to trusted management networks only.
  • Monitor affected assets for abnormal memory growth or service instability.

Validation and detection

  • Compare installed product versions against the affected version ranges.
  • Confirm whether SmartVNC is enabled and network-reachable on affected assets.
  • Verify untrusted networks cannot reach SmartVNC services.
  • Check operational monitoring for denial-of-service symptoms on HMI and drive systems.
  • Review Siemens SSA-538778, SSA-286838, and CISA ICSA-21-131-12 for site-specific guidance.
Prepared
Confidence
high
Sources
5

Generated from the cited source records. This long-tail analysis has not been individually reviewed by a named human.

Potential ATT&CK relevance

Conservative CVE-to-ATT&CK context

These mappings and lookup hints may be relevant to the vulnerability behavior, CWE, affected product, or exposure path. Glexia-inferred context is not an official MITRE, ATT&CK, CWE, or CVE Program mapping.

ATT&CK lookup starting points

Use these exact CWE pages and searches to review the Glexia ATT&CK library from this CVE's weakness and description context.

cwe · low confidence lookup

CWE-770: Exact CWE lookup

Use the exact CWE identifier as the starting point before reviewing related ATT&CK behavior. Open the exact CWE lookup page first, then review the ATT&CK searches from that MITRE weakness context. This is a Glexia lookup hint, not an official ATT&CK mapping.

Open ATT&CK lookup
cve · low confidence lookup

CVE-2021-27383 mapping review

Open the CVE-to-ATT&CK bridge for reviewed, inferred, or future official mappings tied to this CVE.

Open ATT&CK lookup
Vulnerability profileCVE Program record
Severity
High
CVSS
7.5 (3.1)
Known Exploited
No
Published

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Official CVE source material

CNA and ADP enrichment extracted from CVE v5

These fields come from the CVE record and ADP containers, not from Glexia's Take. They preserve time-varying source decisions such as CISA SSVC, KEV status, CVSS metrics, and provider references.

1CVSS vectors
3Timeline events
2ADP providers
4Source links

SSVC decision data

CISA-ADPCISA Coordinator
Timestamp
Version
2.0.3
Exploitation: noneAutomatable: yesTechnical Impact: partial

CVSS vector scores

1 official score

We collect every scored CVSS vector available in the official CNA and ADP containers. When more than one version is present, the table keeps the source vectors side by side instead of collapsing them into the highest score.

ScoreVersionSeverityVectorExploitImpactSource
7.5CVSS 3.1HighCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H3.93.6CISA-ADP

Vulnerability scoring details

Base CVSS 3.1 score

7.5High
CVSS 3.1 vector shape for CVE-2021-27383Attack VectorAttack ComplexityPrivileges RequiredUser InteractionScopeConfidentiality ImpactIntegrity ImpactAvailability Impact

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Attack Vector
NetworkAdjacentLocalPhysical
Attack Complexity
LowHigh
Privileges Required
NoneLowHigh
User Interaction
NoneRequired
Scope
ChangedUnchanged
Confidentiality Impact
HighLowNone
Integrity Impact
HighLowNone
Availability Impact
HighLowNone

Vulnerability timeline

Timeline events are normalized from CVE metadata, CNA source timelines, ADP timelines, and KEV metadata when present.

  1. CVE reservedCVE Program

    The CVE ID was reserved by the assigning CNA.

  2. CVE publishedCVE Program

    The CVE record was published.

  3. CVE updatedCVE Program

    The CVE record metadata indicates this as the latest update time.

ADP provider summaries

CVECVE Program Container
CISA-ADPCISA ADP Vulnrichment
cvssV3_1other:ssvc

Source materials

Affected products

Products and packages named in the record

VendorProductVersion / packageStatus
SiemensSIMATIC HMI Comfort Outdoor Panels V15 7\" & 15\" (incl. SIPLUS variants)All versions < V15.1 Update 6Listed
SiemensSIMATIC HMI Comfort Outdoor Panels V16 7\" & 15\" (incl. SIPLUS variants)All versions < V16 Update 4Listed
SiemensSIMATIC HMI Comfort Panels V15 4\" - 22\" (incl. SIPLUS variants)All versions < V15.1 Update 6Listed
SiemensSIMATIC HMI Comfort Panels V16 4\" - 22\" (incl. SIPLUS variants)All versions < V16 Update 4Listed
SiemensSIMATIC HMI KTP Mobile Panels V15 KTP400F, KTP700, KTP700F, KTP900 and KTP900FAll versions < V15.1 Update 6Listed
SiemensSIMATIC HMI KTP Mobile Panels V16 KTP400F, KTP700, KTP700F, KTP900 and KTP900FAll versions < V16 Update 4Listed
SiemensSIMATIC WinCC Runtime Advanced V15All versions < V15.1 Update 6Listed
SiemensSIMATIC WinCC Runtime Advanced V16All versions < V16 Update 4Listed
SiemensSINAMICS GH150All versionsListed
SiemensSINAMICS GL150 (with option X30)All versionsListed
SiemensSINAMICS GM150 (with option X30)All versionsListed
SiemensSINAMICS SH150All versionsListed
SiemensSINAMICS SL150All versionsListed
SiemensSINAMICS SM120All versionsListed
SiemensSINAMICS SM150All versionsListed
SiemensSINAMICS SM150iAll versionsListed
Weakness

CWE details

CWE links open Glexia weakness intelligence pages with official CWE context, developer remediation guidance, and related CVE mappings.

CWE-770 · source CWE mapping

Allocation of Resources Without Limits or Throttling