CVE-2019-10931: A vulnerability has been identified in All other SIPROTEC 5 device types with CPU variants CP300 and CP100...

A vulnerability has been identified in All other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions ), DIGSI 5 engineering software (All versions < V7.90), SIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.90), SIPROTEC 5 device types 7SS85 and 7KE85 (All versions < V8.01), SIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.59), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.59). Specially crafted packets sent to port 443/TCP could cause a Denial of Service condition.

UnknownCVSS not scoredNot KEV-listedUpdated
Glexia's TakeAutomated analysishigh

Security readout for executives and security teams

Plain-English summary

CVE-2019-10931 affects Siemens SIPROTEC 5 protection devices and DIGSI 5 engineering software. Specially crafted network traffic to HTTPS port 443 can trigger a denial-of-service condition. For power or industrial environments, the concern is loss of availability in protection or engineering systems, not data theft.

Executive priority

Treat this as a high-priority OT availability issue if affected SIPROTEC 5 assets support critical protection functions or are reachable beyond a tightly controlled engineering network. Prioritize inventory, segmentation review, and vendor-guided upgrades or controls.

Technical view

The CVE describes improper handling of exceptional conditions, CWE-248, in listed SIPROTEC 5 CPU variants and Ethernet communication modules, plus DIGSI 5 before V7.90. Crafted packets to 443/TCP may cause DoS. The bundle does not provide CVSS, exploit prerequisites beyond network reachability, or recovery details.

Likely exposure

Exposure is most likely where SIPROTEC 5 management interfaces or DIGSI-related systems are reachable on TCP 443 from engineering, operations, vendor, or broader corporate networks. Internet exposure would materially increase risk, but the supplied sources do not state that affected devices are commonly internet-facing.

Exploitation context

The provided sources do not report active exploitation, and the CVE is not marked KEV. The described attack path is network-based traffic to 443/TCP, so practical risk depends on segmentation, access controls, device versions, and whether affected services are reachable.

Researcher notes

The bundle supports affected product/version ranges and the TCP 443 DoS condition, but lacks CVSS, detailed exploit prerequisites, recovery behavior, and confirmed fixes for every listed all-version category. Avoid assuming exploitation or a universal patch without the Siemens advisory.

Mitigation direction

  • Identify affected SIPROTEC 5 models, CPU variants, Ethernet modules, and DIGSI 5 installations.
  • Upgrade DIGSI 5 to V7.90 or later where applicable.
  • Upgrade listed SIPROTEC 5 devices to the non-affected version thresholds where available.
  • Restrict TCP 443 management access to trusted engineering hosts and networks.
  • Review the Siemens advisory for product-specific compensating controls and unsupported all-version cases.

Validation and detection

  • Inventory SIPROTEC 5 device type, CPU variant, module, and firmware version.
  • Confirm DIGSI 5 versions and compare against the V7.90 threshold.
  • Map which networks can reach affected assets on TCP 443.
  • Check monitoring for unexplained device resets, service loss, or management interface outages.
  • Confirm any compensating controls match Siemens advisory guidance.
Prepared
Confidence
medium
Sources
3

Generated from the cited source records. This long-tail analysis has not been individually reviewed by a named human.

Potential ATT&CK relevance

Conservative CVE-to-ATT&CK context

These mappings and lookup hints may be relevant to the vulnerability behavior, CWE, affected product, or exposure path. Glexia-inferred context is not an official MITRE, ATT&CK, CWE, or CVE Program mapping.

ATT&CK lookup starting points

Use these exact CWE pages and searches to review the Glexia ATT&CK library from this CVE's weakness and description context.

cwe · low confidence lookup

CWE-248: Exact CWE lookup

Use the exact CWE identifier as the starting point before reviewing related ATT&CK behavior. Open the exact CWE lookup page first, then review the ATT&CK searches from that MITRE weakness context. This is a Glexia lookup hint, not an official ATT&CK mapping.

Open ATT&CK lookup
cve · low confidence lookup

CVE-2019-10931 mapping review

Open the CVE-to-ATT&CK bridge for reviewed, inferred, or future official mappings tied to this CVE.

Open ATT&CK lookup
Vulnerability profileCVE Program record
Severity
Unknown
CVSS
Not scored
Known Exploited
No
Published
Official CVE source material

CNA and ADP enrichment extracted from CVE v5

These fields come from the CVE record and ADP containers, not from Glexia's Take. They preserve time-varying source decisions such as CISA SSVC, KEV status, CVSS metrics, and provider references.

0CVSS vectors
0Timeline events
0ADP providers
2Source links

CVSS and timeline data

No CVSS vectors or timeline events were available in the normalized CVE source material.

Source materials

Affected products

Products and packages named in the record

VendorProductVersion / packageStatus
Siemens AGAll other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modulesAll versionsListed
Siemens AGDIGSI 5 engineering softwareAll versions < V7.90Listed
Siemens AGSIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modulesAll versions < V7.90Listed
Siemens AGSIPROTEC 5 device types 7SS85 and 7KE85All versions < V8.01Listed
Siemens AGSIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modulesAll versions < V7.59Listed
Siemens AGSIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modulesAll versions < V7.59Listed
Weakness

CWE details

CWE links open Glexia weakness intelligence pages with official CWE context, developer remediation guidance, and related CVE mappings.

CWE-248 · source CWE mapping

Uncaught Exception

Uncaught Exception represents a recurring weakness pattern that can create exploitable paths when design, validation, or implementation controls are missing.