LiveActive security incident?Get immediate response
CVE Record

CVE-2018-4832: A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versi...

A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS 7 V8.1 (All versions < V8.1 Upd5), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd1), SIMATIC BATCH V7.1 and earlier (All versions), SIMATIC BATCH V8.0 (All versions < V8.0 SP1 Upd21), SIMATIC BATCH V8.1 (All versions < V8.1 SP1 Upd16), SIMATIC BATCH V8.2 (All versions < V8.2 Upd10), SIMATIC BATCH V9.0 (All versions < V9.0 SP1), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions < 15 SP1), SIMATIC PCS 7 V7.1 and earlier (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP1), SIMATIC Route Control V7.1 and earlier (All versions), SIMATIC Route Control V8.0 (All versions), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions < V9.0 Upd1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2 Upd2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1 Upd5), SIMATIC WinCC V7.2 and earlier (All versions < WinCC 7.2 Upd 15), SIMATIC WinCC V7.3 (All versions < WinCC 7.3 Upd 16), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 4), SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.

UnknownCVSS not scoredNot KEV-listedUpdated
Glexia's TakeAutomated analysishigh

Security readout for executives and security teams

Plain-English summary

This Siemens industrial software flaw can let a network-adjacent attacker disrupt communication services on affected application servers. Recovery requires rebooting the system, so the main business risk is operational downtime in environments using SIMATIC, OpenPCS, WinCC, Route Control, or SPPA-T3000 components.

Executive priority

Prioritize remediation where affected Siemens systems support production, safety-adjacent operations, or power generation. The vulnerability is availability-focused, but forced reboot recovery can translate directly into operational downtime.

Technical view

Affected Siemens products mishandle specially crafted messages sent to their RPC service. The result is denial of service against remote and local communication functionality. Exploitation requires network access to the Application Server. The source bundle maps many affected versions to fixed update or service-pack levels.

Likely exposure

Exposure is most likely in industrial control, batch processing, HMI/SCADA, and power plant environments running older Siemens product versions with network-reachable Application Servers.

Exploitation context

The bundle says no public exploitation was known when Siemens published the advisory, and KEV status is false. No cited source in the bundle supports active exploitation.

Researcher notes

Evidence supports RPC-triggered denial of service due to improper input handling, mapped to CWE-20. The bundle does not provide CVSS details, exploit artifacts, or proof of current exploitation, so validation should focus on version exposure and network reachability.

Mitigation direction

  • Upgrade affected Siemens products to the fixed update or service-pack levels listed in the advisory.
  • Restrict network access to Application Servers and RPC services to trusted management and control networks.
  • Review Siemens advisories SSA-451445 and SSA-348629 for product-specific update guidance.
  • Plan maintenance windows because recovery from successful denial of service requires reboot.
  • Monitor vendor guidance for superseding updates or additional mitigations.

Validation and detection

  • Inventory Siemens OpenPCS, SIMATIC, WinCC, Route Control, and SPPA-T3000 deployments.
  • Compare installed versions against the affected and fixed versions in the source bundle.
  • Confirm Application Server RPC services are not reachable from untrusted networks.
  • Review incident logs for unexplained communication loss requiring reboot.
  • Document compensating controls where upgrades cannot be applied quickly.
Prepared
Confidence
high
Sources
4

Generated from the cited source records. This long-tail analysis has not been individually reviewed by a named human.

Potential ATT&CK relevance

Conservative CVE-to-ATT&CK context

These mappings and lookup hints may be relevant to the vulnerability behavior, CWE, affected product, or exposure path. Glexia-inferred context is not an official MITRE, ATT&CK, CWE, or CVE Program mapping.

ATT&CK lookup starting points

Use these exact CWE pages and searches to review the Glexia ATT&CK library from this CVE's weakness and description context.

cwe · low confidence lookup

CWE-20: Exact CWE lookup

Use the exact CWE identifier as the starting point before reviewing related ATT&CK behavior. Open the exact CWE lookup page first, then review the ATT&CK searches from that MITRE weakness context. This is a Glexia lookup hint, not an official ATT&CK mapping.

Open ATT&CK lookup
cve · low confidence lookup

CVE-2018-4832 mapping review

Open the CVE-to-ATT&CK bridge for reviewed, inferred, or future official mappings tied to this CVE.

Open ATT&CK lookup
Vulnerability profileCVE Program record
Severity
Unknown
CVSS
Not scored
Known Exploited
No
Published
Official CVE source material

CNA and ADP enrichment extracted from CVE v5

These fields come from the CVE record and ADP containers, not from Glexia's Take. They preserve time-varying source decisions such as CISA SSVC, KEV status, CVSS metrics, and provider references.

0CVSS vectors
0Timeline events
0ADP providers
3Source links

CVSS and timeline data

No CVSS vectors or timeline events were available in the normalized CVE source material.

Affected products

Products and packages named in the record

VendorProductVersion / packageStatus
SiemensOpenPCS 7 V7.1 and earlierAll versionsListed
SiemensOpenPCS 7 V8.0All versionsListed
SiemensOpenPCS 7 V8.1All versions < V8.1 Upd5Listed
SiemensOpenPCS 7 V8.2All versionsListed
SiemensOpenPCS 7 V9.0All versions < V9.0 Upd1Listed
SiemensSIMATIC BATCH V7.1 and earlierAll versionsListed
SiemensSIMATIC BATCH V8.0All versions < V8.0 SP1 Upd21Listed
SiemensSIMATIC BATCH V8.1All versions < V8.1 SP1 Upd16Listed
SiemensSIMATIC BATCH V8.2All versions < V8.2 Upd10Listed
SiemensSIMATIC BATCH V9.0All versions < V9.0 SP1Listed
SiemensSIMATIC NET PC Software V14All versions < V14 SP1 Update 14Listed
SiemensSIMATIC NET PC Software V15All versions < 15 SP1Listed
SiemensSIMATIC PCS 7 V7.1 and earlierAll versionsListed
SiemensSIMATIC PCS 7 V8.0All versionsListed
SiemensSIMATIC PCS 7 V8.1All versionsListed
SiemensSIMATIC PCS 7 V8.2All versions < V8.2 SP1Listed
SiemensSIMATIC PCS 7 V9.0All versions < V9.0 SP1Listed
SiemensSIMATIC Route Control V7.1 and earlierAll versionsListed
SiemensSIMATIC Route Control V8.0All versionsListed
SiemensSIMATIC Route Control V8.1All versionsListed
SiemensSIMATIC Route Control V8.2All versionsListed
SiemensSIMATIC Route Control V9.0All versions < V9.0 Upd1Listed
SiemensSIMATIC WinCC Runtime Professional V13All versions < V13 SP2 Upd2Listed
SiemensSIMATIC WinCC Runtime Professional V14All versions < V14 SP1 Upd5Listed
SiemensSIMATIC WinCC V7.2 and earlierAll versions < WinCC 7.2 Upd 15Listed
SiemensSIMATIC WinCC V7.3All versions < WinCC 7.3 Upd 16Listed
SiemensSIMATIC WinCC V7.4All versions < V7.4 SP1 Upd 4Listed
SiemensSPPA-T3000 Application ServerAll versions < Service Pack R8.2 SP2Listed
Weakness

CWE details

CWE links open Glexia weakness intelligence pages with official CWE context, developer remediation guidance, and related CVE mappings.