CVE-2016-9154: Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D,...

Siemens Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 for Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D (All firmware versions < V6.00.046) and Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 for Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U (All firmware versions < V6.00.046) use a pseudo random number generator with insufficient entropy to generate certificates for HTTPS, potentially allowing remote attackers to reconstruct the corresponding private key.

UnknownCVSS not scoredNot KEV-listedUpdated
Glexia's TakeAutomated analysis

Security readout for executives and security teams

This flaw affects Siemens Desigo PX Web modules used with building automation controllers. Their HTTPS certificates may be generated with too little randomness, which could let a remote attacker reconstruct the private key. That can undermine trust in the management interface and expose encrypted traffic or impersonation risk. Exposure is most likely in facilities running Siemens Desigo PX Web modules PXA40-W0/W1/W2 or PXA30-W0/W1/W2 on firmware below V6.00.046, especially where the web interface is reachable from corporate, vendor, remote-access, or internet-adjacent networks. Prioritize remediation for exposed building automation management interfaces. The issue can weaken HTTPS trust for operational technology systems, but the provided sources do not show active exploitation. Mitigation focus: Upgrade affected Desigo PX Web modules to firmware V6.00.046 or later where applicable.; Review Siemens advisory SSA-856492 before making operational changes.; Restrict web management access to trusted management networks only..

Prepared

Generated from the cited source records. This long-tail analysis has not been individually reviewed by a named human.

Potential ATT&CK relevance

Conservative CVE-to-ATT&CK context

These mappings and lookup hints may be relevant to the vulnerability behavior, CWE, affected product, or exposure path. Glexia-inferred context is not an official MITRE, ATT&CK, CWE, or CVE Program mapping.

ATT&CK lookup starting points

Use these exact CWE pages and searches to review the Glexia ATT&CK library from this CVE's weakness and description context.

cwe · low confidence lookup

CWE-332: Exact CWE lookup

Use the exact CWE identifier as the starting point before reviewing related ATT&CK behavior. Open the exact CWE lookup page first, then review the ATT&CK searches from that MITRE weakness context. This is a Glexia lookup hint, not an official ATT&CK mapping.

Open ATT&CK lookup
cve · low confidence lookup

CVE-2016-9154 mapping review

Open the CVE-to-ATT&CK bridge for reviewed, inferred, or future official mappings tied to this CVE.

Open ATT&CK lookup
Vulnerability profileCVE Program record
Severity
Unknown
CVSS
Not scored
Known Exploited
No
Published
Official CVE source material

CNA and ADP enrichment extracted from CVE v5

These fields come from the CVE record and ADP containers, not from Glexia's Take. They preserve time-varying source decisions such as CISA SSVC, KEV status, CVSS metrics, and provider references.

0CVSS vectors
0Timeline events
0ADP providers
2Source links

CVSS and timeline data

No CVSS vectors or timeline events were available in the normalized CVE source material.

Source materials

Affected products

Products and packages named in the record

VendorProductVersion / packageStatus
n/aDesigo PX Web modules with all firmware versions < V6.00.046Desigo PX Web modules with all firmware versions < V6.00.046Listed
Weakness

CWE details

CWE links open Glexia weakness intelligence pages with official CWE context, developer remediation guidance, and related CVE mappings.

CWE-332 · source CWE mapping

Insufficient Entropy in PRNG

Insufficient Entropy in PRNG represents a recurring weakness pattern that can create exploitable paths when design, validation, or implementation controls are missing.