LiveActive security incident?Get immediate response
MITRE ATT&CK® Reference

Detections

Detection strategies and analytics from ATT&CK where present.

3,216 records · validated library

Detections results

Results are validated against normalized ATT&CK source records when available; sample records are used only in development or empty-data environments.

AnalyticICS

AN2152: Analytic 2152

Real-time monitoring identifies system binaries (bash, python, perl, awk, dd) on Industrial Control System (ICS) Linux assets executing with arguments that pipe or decode external content rather than performing their documented administrative function. OT operational-fidelity gate: Alert only when execution violates an approved signer/hash/path/parent/process or tool allowlist, or originates from an unauthorized user/tool, and is tied to an OT asset or follow-on OT-relevant action. Suppress vendor-signed software, approved engineering utilities, diagnostics, patching, backup, and documented maintenance.

Linux
AnalyticICS

AN2153: Analytic 2153

Real-time monitoring identifies a Linux process making Open Platform Communications (OPC) Unified Architecture (UA) write calls or direct Industrial Control System (ICS) protocol command connections to field device output addresses, from a User Identifier (UID) not associated with the authorized control application. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Linux
AnalyticICS

AN2154: Analytic 2154

Real-time monitoring identifies ptrace syscalls or /proc/pid/mem write operations targeting Industrial Control System (ICS) service processes from a process that is not a debugger or vendor diagnostic tool. OT operational-fidelity gate: Alert only when execution violates an approved signer/hash/path/parent/process or tool allowlist, or originates from an unauthorized user/tool, and is tied to an OT asset or follow-on OT-relevant action. Suppress vendor-signed software, approved engineering utilities, diagnostics, patching, backup, and documented maintenance.

Linux
AnalyticICS

AN2155: Analytic 2155

Real-time monitoring identifies Industrial Control System (ICS) Linux service processes initiating outbound application-layer protocol connections to ports/destinations outside the approved communication matrix. OT operational-fidelity gate: Alert only when the asset's documented role does not permit the connection and the destination/proxy/service is outside the approved communications profile, with process/service identity used as corroboration where available. Suppress approved vendor support, update repositories, remote operations, failover paths, and documented temporary connectivity.

Linux
AnalyticICS

AN2156: Analytic 2156

Real-time monitoring identifies a process opening a raw socket or executing tcpdump/tshark on an Industrial Control System (ICS) Linux asset's network interface, from a User Identifier (UID) that does not normally perform packet capture. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Linux
AnalyticICS

AN2157: Analytic 2157

Real-time monitoring identifies an Industrial Control System (ICS) Linux engineering tool issuing device restart commands outside a scheduled maintenance window, from a User Identifier (UID) not in the approved engineer list. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Linux
AnalyticICS

AN2158: Analytic 2158

Real-time monitoring identifies a firmware update tool on an Industrial Control System (ICS) Linux engineering host initiating firmware-update mode activation outside a scheduled maintenance window, by a User Identifier (UID) not in the approved firmware manager UIDs. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Linux
AnalyticICS

AN2159: Analytic 2159

Real-time monitoring identifies SSH lateral movement between Industrial Control System (ICS) Linux hosts not in the documented communication matrix, with subsequent ICS tool execution or privilege escalation. OT operational-fidelity gate: Alert only when the account/device/session violates the approved identity + source host/jump path/zone policy and is corroborated by access to a protected OT asset, execution, configuration change, or another security-relevant follow-on event. Suppress approved shift activity, vendor support, break-glass use, commissioning, and documented remote-access windows.

Linux
AnalyticICS

AN2160: Analytic 2160

Real-time monitoring identifies an Industrial Control System (ICS) protocol library loaded by a Linux process not in the authorized ICS applications list, making connections to the device subnet. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Linux
AnalyticICS

AN2161: Analytic 2161

Real-time monitoring identifies execve of port scanning utilities on an Industrial Control System (ICS) Linux asset with arguments targeting ICS protocol port ranges. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Linux
AnalyticICS

AN2162: Analytic 2162

Real-time monitoring identifies a Linux process sending User Datagram Protocol (UDP) broadcast packets to Industrial Control System (ICS) discovery addresses from a User Identifier (UID) not associated with any recognized ICS commissioning tool. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Linux
AnalyticICS

AN2163: Analytic 2163

Real-time monitoring identifies a Linux process joining Industrial Control System (ICS) multicast groups via socket() with IP_ADD_MEMBERSHIP, from a User Identifier (UID) not associated with any authorized ICS protection system monitoring application. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Linux
AnalyticICS

AN2164: Analytic 2164

Real-time monitoring identifies iptables/nftables rule additions blocking Industrial Control System (ICS) protocol ports on Linux ICS gateways. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Linux
AnalyticICS

AN2165: Analytic 2165

Real-time monitoring identifies ip link set down commands on Industrial Control System (ICS) Linux gateway hosts by a User Identifier (UID) not in the authorized net admin UIDs, affecting the device subnet interface. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Linux
AnalyticICS

AN2166: Analytic 2166

Real-time monitoring identifies hostapd or wireless controller configuration changes on Linux-based access points disabling the Industrial Control System (ICS) wireless Service Set Identifier (SSID), by a User Identifier (UID) not in the authorized wireless admin UIDs. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Linux
AnalyticICS

AN2167: Analytic 2167

Real-time monitoring identifies Industrial Control System (ICS) host telemetry gaps -- process lists differing between Windows Management Instrumentation (WMI) and direct enumeration, or unexpected kernel driver loads from unexpected paths -- suggesting kernel-level manipulation of what the Operating System (OS) reports. OT operational-fidelity gate: Alert only when execution violates an approved signer/hash/path/parent/process or tool allowlist, or originates from an unauthorized user/tool, and is tied to an OT asset or follow-on OT-relevant action. Suppress vendor-signed software, approved engineering utilities, diagnostics, patching, backup, and documented maintenance.

Windows
AnalyticICS

AN2168: Analytic 2168

Real-time monitoring of switch/router interface counters identifies a sudden spike in discarded or errored packets on an Industrial Control System (ICS)-facing interface combined with Central Processing Unit (CPU) utilization climbing above baseline, correlated with loss of reachability to downstream field devices on that segment within the same window. OT operational-fidelity gate: Alert only when a device-specific traffic/resource threshold is exceeded and the same window shows service degradation, failed polling, device alarm/restart, resource exhaustion, or malformed/out-of-spec protocol behavior. Suppress planned load tests, maintenance, network convergence/failover, and known equipment faults after operator confirmation.

Network Devices
AnalyticICS

AN2169: Analytic 2169

Real-time monitoring identifies NetFlow showing a host generating an anomalously high volume of short-duration flows to multiple field device IPs at regular intervals, from a source not in the approved Supervisory Control and Data Acquisition (SCADA) server list. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Network Devices
AnalyticICS

AN2170: Analytic 2170

Real-time monitoring identifies vendor-specific firmware-update protocol traffic to ICS device IP addresses from a source not in the approved engineering-workstation or firmware-management baseline. OT operational-fidelity gate: Alert only when the action is not attributable to an authorized operator/engineering source for the specific target and function, and it is either outside an approved change/maintenance window or lacks matching change-control context; where telemetry permits, require corroborating device, configuration, or process-state effect. Suppress activity that fully matches approved maintenance, commissioning, failover, recovery, or tested control procedures.

Network Devices
AnalyticICS

AN2171: Analytic 2171

Real-time network monitoring identifies a source generating Industrial Control System (ICS) discovery broadcasts or sequential connection attempts across the full IP range of a device subnet, from a source not in the approved engineering/Supervisory Control and Data Acquisition (SCADA) inventory. Documented in the PIPEDREAM/INCONTROLLER toolset's CODECALL module for EtherNet/IP device discovery. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Embedded
AnalyticICS

AN2172: Analytic 2172

Real-time monitoring identifies Internet Control Message Protocol (ICMP) echo sweeps, Address Resolution Protocol (ARP) broadcast floods, or Industrial Control System (ICS)-specific discovery protocol packets from a host generating traffic to all IPs in a subnet in sequential order, a sweep pattern distinct from normal operational traffic to known device Internet Protocol (IP) addresses only. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Network Devices
AnalyticICS

AN2173: Analytic 2173

Real-time monitoring identifies exploit-pattern HTTP/HTTPS traffic targeting an ICS DMZ application from a source or request pattern outside the approved application baseline. OT operational-fidelity gate: Alert only when execution violates an approved signer/hash/path/parent/process or tool allowlist, or originates from an unauthorized user/tool, and is tied to an OT asset or follow-on OT-relevant action. Suppress vendor-signed software, approved engineering utilities, diagnostics, patching, backup, and documented maintenance.

Network Devices
AnalyticICS

AN2174: Analytic 2174

Real-time monitoring identifies large outbound data transfers from Industrial Control System (ICS) server Internet Protocol (IP) addresses to destinations outside the approved ICS zone, following a pattern of bulk reads from engineering document stores or historian databases. OT operational-fidelity gate: Do not alert on novelty, scan/read volume, or enumeration alone. Alert when the source role is not authorized for discovery/polling and the target scope, address/tag range, protocol, or rate deviates from the established operational baseline. Suppress normal SCADA/HMI/historian polling, commissioning, asset inventory, backup, diagnostics, and approved engineering activity.

Network Devices
AnalyticICS

AN2175: Analytic 2175

Real-time monitoring identifies a host simultaneously maintaining an inbound connection on an Industrial Control System (ICS) protocol port and an outbound connection to a destination outside the ICS network zone, detectable as correlated dual flows with matching timing and approximate byte-count proportionality. OT operational-fidelity gate: Alert only when the asset's documented role does not permit the connection and the destination/proxy/service is outside the approved communications profile, with process/service identity used as corroboration where available. Suppress approved vendor support, update repositories, remote operations, failover paths, and documented temporary connectivity.

Network Devices
AnalyticICS

AN2176: Analytic 2176

Real-time monitoring identifies network device configuration changes (network address translation rules, static routes, access control list modifications) combined with NetFlow path deviations for Industrial Control System (ICS) device traffic and Transport Layer Security (TLS) certificate issuer anomalies in Operational Technology (OT) management traffic. OT operational-fidelity gate: Alert only when the asset's documented role does not permit the connection and the destination/proxy/service is outside the approved communications profile, with process/service identity used as corroboration where available. Suppress approved vendor support, update repositories, remote operations, failover paths, and documented temporary connectivity.

Network Devices
Source and licensing